Configure the PHANTOM® Gateway

availability
Feature availability by platform, plan type, and user type
Platform:AvailableWebNot availableMobile
Plan Type:Not availableBasicNot availableEssentialAvailablePremiumAvailableEnterprise
User Type:Not availableRequesterNot availableFull UserAvailableAdministrator

Configure the ERBESSD INSTRUMENTS® PHANTOM Gateway to push sensor data to MaintainX®. These steps take place on the gateway or in the ERBESSD INSTRUMENTS software, except for verifying data in MaintainX.

Prerequisites​

  • MaintainX connector token: Generated when you create a connector instance in MaintainX. For more information, see Set Up the ERBESSD INSTRUMENTS Integration.
  • Gateway access: Depending on your setup, either an EI Analytics account connected to the target gateway, or a computer on the same network as the gateway to use its local admin interface.
note

The steps below use EI Analytics Gateway Manager. If you don't have EI Analytics access, you can make the same changes directly on the gateway's local admin interface instead.

Update the Gateway Firmware​

The PHANTOM Gateway requires firmware version 56 or later.

  1. Log in to app.eianalytic.com, and then select Database > Gateway Manager.
  2. Find your target gateway and select the link under Admin console.
  3. In the admin console, select System tools > System firmware update.
  4. Select Check online status to check for an available firmware update. If one is available, select Update.

Point the Gateway at MaintainX​

  1. In the Gateway Manager, select Config.

  2. Select Send data to custom Cloud.

  3. Enter the following settings:

    • POST request format: JSON format
    • Custom Cloud endpoint URL: https://agent.maintainx.com/agent/phantom/payload
    • Auth token: The connector instance token you copied in MaintainX.
  4. Save your settings. The gateway reboots to reload your changes.

When the gateway successfully sends its first payload to MaintainX, the following things happen:

  • The gateway status updates to Cloud: OK.
  • In MaintainX, the connector instance changes from Waiting for Connection to Connected.
My gateway status still says Cloud: FAIL

When you first save the gateway settings, the status might still show Cloud: FAIL, even if the URL and token are correct. This is expected behavior. The status doesn't update until a sensor is paired and the gateway receives its first payload from it.

Verify Data Is Flowing​

After MaintainX registers a sensor, confirm that readings are reaching MaintainX.

  1. From the sidebar, select Asset Monitoring > Meters.
  2. From the list, find a meter whose name is prefixed with the registered sensor's serial number.
  3. Select the meter to open it.
  4. In the Readings section, select See All Readings to confirm new readings are arriving.

Allow up to one hour after the PHANTOM Gateway connects for the first readings to arrive. After that, readings arrive as the sensor reports new data. If no readings appear, see Not Seeing Data in MaintainX.